top of page
logo-new-2017.png

Home

Agent Release Panel (RE-120GR)

Panel-2 Zone Agent Release Panel (RE-120GR)

Panel-2 Zone  Agent Release Panel (RE-120GR)

Panel-2 Zone Agent Release Panel (RE-120GR)

Panel-2 Zone Agent Release Panel (RE-120GR)

Product Warranty

One Year Warranty

Specification:

  • Ravel Indian Manufacturer, International standard.
    Modular Construction, Serviceable.
    Special logic circuitory to prevent accident release.
    Auto Resettable Fuse.
    Surge Protected.
    Battery polarity & deep discharge protection.
    Variable solenoid ON / OFF time.
    2 No’s of programmable Initiating Device Circuit and 1 No’s of Releasing Agent circuit.
    Operates on 220V, A.C supply
    Battery backup with built in charging.
    16 X 2 LCD Dot Matrix Display.
    Evacuate and Key pad Enable, Disable Facility.
    Low battery visual warning with audible tone.
    Relay output for actuators.
    Provision for Remote fire with Audio / Visual Indications.
    Compatible to all types of conventional detectors.
    Zone Disable (Isolation) facility with loop voltage cut off.
    Resettable 24v DC output for 4 wire detectors.
    Three 24V Sounder Output (Fire, after Cross zone, after gas release).
    Two mode operation facility (Auto / Manual).
    Programmable Solenoid Output with ON and OFF Timer.
    Programmable Main / Standby Cylinder output Facility.
    Gas Inhibit and Instant release facility.
    Manual Gas Release with or without timer.
    Actuator pressure low sensing facility.
    RS 485 Output for Repeater.

  • Electrical Specification:

Power
220-240 VAC, 50 Hz.
Wire size   :   1.5 Sq. mm with 600V insulationReleasing Agent Circuit
Operating Nominal Voltage   :   24 VDC
Solenoid output   :   0.75A
End-Of-Line Resistor   :   4.7K, 1/4watt (for Solenoid Output)Battery (Lead Acid only)
Charging Voltage   :   28 VDC.
Charging Current   :   0.5 Amps (Max)
System Quiescent Current   :   100mARemote Outputs
1 Form C relay for Fire, Fault and Cross Zoning.
Contact Rating   :   2A @ 30 VDC & 0.5 A @125VAC.Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring
Normal Operating Voltage   :   14 – 21 VDC
Alarm Current   :   15 – 30mA
Short Circuit Current   :   40mA Maximum
Loop resistance   :   50 ohms Maximum
End-Of-Line Resistor   :   4.7K, 1/4watt
Standby Current   :   6.8mA (2.4mA for Detectors)24 VDC Power For remote devices (Optional)
Operating Voltage   :   24VDC, 300mA Max.Operating Condition
Operating Temperature 0 – 49° C / 32-120° F.
Relative Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ± 3° F.Notification Appliance Circuits (Sounder / Strobe Circuit)1) Supervised:1 NoOperating Nominal Voltage:24 VDCOperating Current:0.75A (Max)End-Of-Line Resistor:4.7K, 1/4watt   2) Non – Supervised:2 No’sOperating Nominal Voltage:24 VDCOperating Current:0.3A (Max)End-Of-Line Resistor:4.7K, 1/4wattMechanical Specification
Dimensions:(400W X 300H X 100D)Color:Red / WhiteConstruction:18 Gauge (1.22mm) CRCA sheet with powder-coated FinishIP Rating:IP50Cable Entry:09 x ø19mm Knockout in top of the cabinet WeightWeight:7 KgCompatible Devices
ModelDescriptionRE-Monitor24VDC Output for Monitor ModuleRE-4K7End Of Line ResistorOrdering Information
ModelDescriptionRE-120GR-W2 ZONE Gas Release PanelRE-120GR-R2 ZONE Gas Release PanelNote:
R – Red Color ; W – White Color ;