Home
RE-900 Series
Panel RE-900 Series
Panel RE-900 Series
Product Warranty
One Year Warranty
Panel RE-900 Series
Specification:
Complies with UL -864 and NFPA-72.
20 x 4 Dot Matrix LCD Display.
Operates on 120 – 220v 60 /50 Hz, AC Mains power supply.
Standby (battery) backup 24v DC power supply with builtin charger.
Touch Keypad for user friendly operation.
Epoxy powder coated finish.
Class- B, Style B / C initiating device circuit (IDC).
All zones accept smoke detectors and any normally open contact device.
Class B Notification Appliance Circuits (NAC).
NAC shall be programmed as auto silence / Silence Inhibit.
Error free Fire / Fault status in unambiguous colored LED indication.
1000 Event storage with RTC.
Main, Standby status with audible and visual indication.
Two Form C relays for fire and fault.
Resettable / Steady 24V D.C. Output.
RS 485 Communication facility.
TCP/IP facility (Optional)
MODBUS for BMS integration (Optional).
PC software (optional)
External Zone Wise Sounder/Contact via RS 485 (Optional).
All field wiring circuits are supervised.
Zone Isolation facility with loop voltage cut off.
Zones available : 12, 16, 20, 24, 32, 48, 64,96 and 128.
Facility to connect Public Address System (PA) through RS-485 Communication.
Peer to Peer network facility.
Maximum 16 panels can be connect in a Single Network.
ModelDescriptionRE-900RP SeriesFire Alarm Repeater PanelElectrical Specification
Primary Power
120 – 220VAC ± 10%, 60 / 50 Hz.Initiating Device Circuits
All zones are
Class B Style B/C operation (Programmable).
Normal Operating Voltage : 14 – 21 VDC.
Alarm Current : 15 – 30mA.
Short Circuit Current : 45mA Maximum.
Loop resistance : 100 ohms Maximum.
End-Of-Line Resistor : 4K7, 1/2watt
Standby Current : 7mA (2.5mA for Detectors)Standby Power
24V D.C
Quiescent current : 120 mAOperating Condition
Operating Temperature : 0 – 49° C/32-120° F.
Relative Humidity : 93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F. Charging Circuit
Charging Voltage : 28.0V, ±0.5V
Charging Current : 1.2A(Max);D.C. Output(Resettable / Steady)
24VDC Output ,1A Max.Common Relays
Type : Form C
No of Relays : 2
Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @ 125VAC.
Power Factor : 1.0Notification Appliance Circuits
Class B Style – Y wiring
Operating Nominal Voltage : 24VDC
Special Application Current : from 12 Zone Upto 64Zone
NACs : 2 Amps (1 A per circuit) Current above 64Zone
NACs : 4 Amps (1 A per circuit)
Line Drop : 1.8V
End-Of-Line Resistor : 4K7, 1/2wattDimensions
ZonesWidthHeightDepth12 Zone42535012016 Zone42535012020 Zone50060016024 Zone50060016032 Zone50060016048 Zone60070016064 Zone600100016096 Zone6001400160128 Zone6001400160Ordering Information
ModelsDescriptionRE-901212 Zone Fire Alarm Control PanelRE-901616 Zone Fire Alarm Control PanelRE-902020 Zone Fire Alarm Control PanelRE-902424 Zone Fire Alarm Control PanelRE-903232 Zone Fire Alarm Control PanelRE-904848 Zone Fire Alarm Control PanelRE-906464 Zone Fire Alarm Control PanelRE-909696 Zone Fire Alarm Control PanelRE-9128128 Zone Fire Alarm Control PanelCompatible Devices