Specification:
Features:
Indian Manufacturer – International standard.
UL Certified (9th Edition)
Touch Keypad for user friendly operation.
Inbuilt USB.
Universal Switched Mode Power Supply.
Modular Construction, Serviceability.
Networkable.
Auto Resettable Fuse.
Electrical Specification
Primary Power
120 / 220VAC + 10% -15%, 60 / 50 HzProgrammable Relays
Type : Form C
No of Relays : 3
Relay Contact Rating : 2A @ 30 VDC,
0.5A @ 125VAC.Standby Power
24V D.C (2 No’s of 12V, 40 Ah (Max), Built in for 12Ah)
Sealed Lead acid batterySignaling Line Circuits
Loop card : 4 Nos. Maximum.
No Devices per loop : 254
Loop resistance : 40Ω (Max.).
Loop capacitance : 0.6 µf (Max.).
Loop Current : 300mA (Max.).Charging Circuit Charging Voltage 28 V, ±0.2V Nominal
Charging Current 1.2A (Max.).Initiating Device Circuits
Class B Style B/C Operation.
No of Conventional Zone : 1
Normal Operating Voltage : 14 – 21 VDC.
Alarm Current : 15 – 30mA.
Short Circuit Current : 45mA Maximum.
Loop resistance : 100Ω Maximum.
End-Of-Line Resistor : 4K7, 1/2watt
Standby Current : 7mA (2mA for Detectors)Notification Appliance Circuits
No of circuits : 2
Class B, Style – Y wiring
Operating Nominal Voltage : 24 VDC Nominal
Current for NACs :
NAC – 1 : 0.9A
NAC – 2 : 0.9 A
Line Drop : 2.4V
End-Of-Line Resistor : 4K7, ½ watt
D.C. Output
Supervised 24VDC, 300mA Max.Programmable Input Circuit
Normal Operating Voltage : 4 – 8 VDC.
Short Circuit Current : 3mA Maximum.
Loop resistance : 100Ω Maximum.
End-Of-Line Resistor : 4K7, 1/2watt
Standby Current : 1.25mA
Mechanical Specification
Dimensions:(400W X 500H X 120D)mmColor:White / Red / BlackConstruction:16 Gauge (1.6 mm) CRCA sheet with powder-coated FinishIP Rating:IP50Cable Entry:9xø19mm Knockout in top of the cabinet
9xø22.25mm Knockout in top of the cabinetWeight:13 Kg